Ok, since your High side or head pressure is normal or with-in range. We can safely assume the system is not low and there’s probably no restriction in the lines.
Now your suction pressure is low so let’s review the possible causes of a low suction.
1 – Low on charge, but no that would cause a low head also.
2 – Restriction but, that would cause a high head pressure
3 – Lack of airflow across the evaporator coil will cause a low suction also. There are many causes of low airflow. No blower motor, dirty coil, dirty filter or a crushed duct.
But, in the beginning you verified that your blower motor was running and you already checked the air filter. So that leaves two choices a dirty coil or a crushed duct.
Go to the indoor unit and double check that the blower motor is running by sound and vibration.